Type keywords to search pages, products, standards and articles
Gas-purged thermocouple
Applications
Tel: 0512-57892201 Mobile: 13451695112
The operating principle of the gas-purged thermocouple is to form a gas path between the MI thermocouple sensing element and the outer protection tube. An inert gas at a certain pressure is introduced into this path to expel or reduce the ingress of reducing gases under high-temperature and high-pressure conditions. The addition of a trace amount of tantalum improves the gettering property of the gas-purged thermocouple, thereby extending the service life of the MI thermocouple. It is an indispensable temperature measuring device in 300 000 t/a ammonia synthesis plants.
○ Electrical outlet: M20×1.5,NPT1/2
○ Ingress protection:IP65
○ Purging pressure: 0.1 MPa
○ Nominal pressure:2.5MPa
Model & Specification
2) Other protection tube materials are supplied per agreement,
3) Flanges can be supplied per agreement.
For selection guidance, specification confirmation or quotation, please call 0512-57892201, Mobile 13451695112, or submit an online order. Suzhou Dingluxuan Sensor Technology Co., Ltd. provides a complete matching service from temperature sensing elements to complementary ceramic insulation parts.
To order this product or get selection guidance, please call +86 512-57892201 or submit an online order.