A field troubleshooting guide for temperature measurement faults. Each fault class is listed in order of likelihood.

Open circuit (controller displays “OPEN” or “−−−−”)

Possible cause Diagnostic test Fix
1. Thermocouple wire break Measure the resistance at the controller end (open TC). A short sensor <10Ω and a long MI cable <50Ω; above 1kΩ or ∞ means a break. Replace the thermocouple. Common break points: the furnace outlet (thermal cycling fatigue) and the compression ferrule (over-tightened).
2. Loose terminals Wiggle the wires at the controller and sensor ends; if “OPEN” appears intermittently, the connection is loose. Tighten the terminal screws; if corroded/oxidised, cut back 10 mm and re-terminate, using ferrules for stranded wire.
3. Extension wire break Measure open-circuit from the controller to the sensor end; ∞ means a break; check along the routing for crushed/cut sections. Replace the cable. Vulnerable points: sharp edges of cable trays, equipment pressing down, rodent damage.
4. Thermocoupleburnout If the furnace exceeds the TC upper limit (e.g. Type K at 1450°C), the wires melt/oxidise and break inside the sheath. Replace with the correct type (>1350°C use R/S); check the controller log for overtemperature events.
5. controllerinputfault Swap the channel: if the fault follows the TC, the TC is bad; if it stays in place, the channel is bad. Replace the input card/module — less common than field cable faults but it still happens.

Reading drift / inaccurate (wrong by 10–50°C)

Possible cause Diagnostic test Fix
1. Wrong extension-wire type Check the label and confirm the type matches; the error is constant (always +X or −X at all temperatures). Replace with the correct type. See section 3 — the most common field error.
2. Thermocoupledrift(High temperatureaging) Compare against a known-good reference TC or calibration instrument; Type K drifts −5 to −15°C after 1000 h above 1000°C. Replace the thermocouple; the drift is permanent (metallurgical change); Type N drifts less, so schedule replacements.
3. Cold-junction compensation error Check the controller’s cold-junction sensor; it should read room temperature (20–25°C); if not, the CJC is faulty. Replace the controller or recalibrate the CJC; some controllers have a CJC offset adjustment in the setup menu.
4. Out of calibration (contamination) Noble-metal TC (R/S/B) contaminated by metal vapour, silicon or carbon; the wire discolours (Grey to Brown/Black) and is permanently damaged. Replace the TC; prevention: high-purity alumina protection tubes, avoid reducing atmospheres, keep vacuum chambers clean.
5. Sheath grounding (Type K ”green rot”) Moisture + oxygen enter the sheath (porous ceramic insulation); Chromel oxidises to chromic oxide (green powder); an ohmmeter reading TC-to-sheath <100 Ohm indicates grounding. Replace the TC; prevention: seal the sheath (welded tip), avoid thermal cycling below 500°C (condensation), use Type N (more resistant).

Noise / jumping (random jumps of ±5–20°C)

Possible cause Diagnostic test Fix
1. Electrical noise pickup Switch off nearby VFDs, welding machines and contactors; if the noise stops, it is EMI; TC cable running parallel to power cable = an antenna. Use shielded TC cable; ground the shield layer at one end only; keep at least 300 mm away from power cables. See section 7.
2. Intermittent connection Tap the cable, wiggle the terminals and flex the cable near the furnace outlet; if the reading jumps, the connection is bad. Re-terminate the cable ends; replace over-tightened compression ferrules (crushed wire = intermittent) and check for oxidation.
3. Ground loop Measure the TC to earth at both the sensor and controller ends; multiple grounding points mean current flows through the TC = false voltage. Isolate the TC and sheath (insulating ferrule); ground the sheath at one point only, never at both ends.
4. Water ingress Check the terminal box for condensation; moisture creates a low-resistance path between the positive and negative wires (a virtual short). Dry out the terminal box and seal the entry; if water has entered the MI cable sheath, replace it (cannot be dried, must be replaced).

Slow response (sensor lags the actual temperature)

Possible cause Diagnostic test Fix
1. Large thermal mass (thick sheath) Check the diameter: a 12 mm MI cable responds in 10–30 s, a 3 mm one in 1–3 s. Use a finer TC or a bare junction (fastest but brittle), trading speed against durability.
2. Protection-tube air gap Poor TC-to-protection-tube contact; the air gap insulates and makes the sensor deviate from the process temperature. Use a thermally conductive filler sleeve (graphite powder, thermal conductive paste), or a spring-loaded TC to maintain contact.
3. Low flow velocity (poor convection) Still air and stagnant liquid transfer heat extremely slowly; flowing fluids respond quickly. Increase the flow velocity around the sensor, mount it in the flow path rather than a dead zone, and add baffles.

Dingluxuan Sensor Technology

Design, manufacturing and sales of temperature, pressure and humidity sensors, instruments and ceramic products — delivering integrated temperature-measurement and control solutions.

Products

Products

Applications

Applications

Contact Us

Contact
No. 828 Xueyuan Road, Bacheng Town, Kunshan City, Jiangsu, China
Tel
0512-57892201
Mobile: 13451695112
Email: yanghui@dingluxuan.com
Copyright©2017-2026  Suzhou Dingluxuan Sensor Technology Co., Ltd.   苏ICP备17068273号-1
中文EN
中文EN